Deck 19: Specific Equipment

Full screen (f)
exit full mode
Question
Article 647 covers the installation and wiring of sensitive electronic equipment that is connected to a separately derived system operating at ____ volts line-to-line and 60 volts to ground.

A) 100
B) 112
C) 120
D) 180
Use Space or
up arrow
down arrow
to flip the card.
Question
Each hoistway elevator pit shall have at least one ____-volt, single phase, 15- or 20-ampere duplex receptacle

A) 100
B) 120
C) 125
D) 140
Question
An electric vehicle supply equipment's coupling means shall be stored or located at a height of not less than ____ in. above the floor level for indoor locations and 24 in. above the grade level for outdoor locations.

A) 12
B) 14
C) 18
D) 24
Question
Individual office furnishings of the freestanding type, or groups of individual office furnishings that are electrically connected, are mechanically contiguous, and do not exceed 30 ft when assembled, shall be permitted to connect to the building's electrical system by means of a ____.

A) single flexible cord and plug
B) rigid raceway
C) surge protector and concealed wiring
D) dual flexible cable and panel board
Question
Electric signs and outline lighting systems shall be marked with the manufacturer's name, trademark or other identification, ____, and current rating.

A) input voltage
B) output wattage
C) potential lumens
D) average load
Question
Equipment used to combine and level-match a multiplicity of electronic signals, as from microphones, electronic instruments, and recorded audio is referred to as a(n) ____.

A) panel board
B) mixer
C) audio swapper
D) signal transformer
Question
Conductors in pipe organs shall have ____ insulation.

A) standard polymer
B) thermoplastic or thermosetting
C) thermoelastic or thermo-molded
D) hybrid plastic/polymer
Question
Circuit voltage of heating/air-conditioning equipment branch circuits located on the elevator car shall not exceed ____ volts.

A) 500
B) 600
C) 800
D) 1000
Question
A separately derived ____ with 60 volts on each of two ungrounded conductors to a grounded neutral conductor can be used to reduce objectionable noise in sensitive electronic equipment locations.

A) 110-volt, single-phase, 3-wire system
B) 115-volt, single-phase, 3-wire system
C) 120-volt, single-phase, 3-wire system
D) 125-volt, single-phase, 3-wire system
Question
Flexible metal conduit, ____ metal conduit, liquidtight flexible nonmetallic conduit, and flexible cords and cables are permitted wiring methods are permitted on the counterweight assembly and on the car assembly in elevators.

A) rigid sealed
B) flexible hybrid
C) liquidtight flexible
D) liquidtight rigid
Question
Branch circuits and feeders in a separately derived 60-volts to ground system shall be provided with a means to ____.

A) prevent current surges
B) simultaneously disconnect all ungrounded conductors
C) protect from lightening discharges
D) permit service access
Question
LFNC of ____ in. nominal trade size or larger, as defined in 356.2(2), can be installed in escalators or moving walkways in lengths greater than 6 ft.

A) 1/4
B) 3/8
C) 5/8
D) 3/4
Question
Neon tubing's length and design shall not cause a continuous overcurrent beyond the capacity of the transformer or ____.

A) surge protection
B) disconnecting means
C) electronic power supply
D) branch circuit
Question
Electric signs and outline lighting system equipment in wet locations, unless of the listed watertight type, shall be weatherproof and, if necessary, have ____ in accordance with 600.9(D)(1) through (3).

A) surge protection
B) lightening protection
C) a front-mounted disconnect
D) drain holes
Question
The minimum conductor size for traveling cables that feed lighting circuits is ____ AWG copper.

A) 14
B) 16
C) 18
D) 20
Question
Neon tubing secondary conductor(s) shall be supported within ____ in.of the electrode connection.

A) 4
B) 6
C) 12
D) 18
Question
A luminaire intended for installation in a pool or fountain structure's forming shell, where completely surrounded by water is referred to as ____.

A) a wet niche luminaire
B) aquatic luminaire
C) forming shell
D) packaged source
Question
A pipe organ should use a minimum of ____ AWG conductors for electronic signal circuits, and at least 26 AWG for electromagnetic valve supply.

A) 24
B) 26
C) 28
D) 30
Question
All ____ receptacle outlets used in technical applications shall be GFCI protected.

A) 15- and 20-ampere
B) 15- and 25-ampere
C) 15- and 30-ampere
D) 20- and 30-ampere
Question
The power source for a pipe organ shall be a transformer-type rectifier having a direct current (dc) potential of ____ volts or less.

A) 10
B) 20
C) 25
D) 30
Question
Unit heaters shall not be mounted over the pool or`within the area extending ____ ft horizontally from the inside walls of a pool.

A) 5
B) 6
C) 8
D) 9
Question
Unencapsulated structural reinforcing steel in pools shall be ____.

A) bonded together by steel tie wires or the equivalent
B) grounded via rigid wire cables to an earth ground
C) bonded using equipotential bonding
D) encased in corrosion-resistant materials
Question
Equipotential bonding required by 680.26 shall be installed to reduce ____ in the pool area.

A) power surges
B) shorting
C) load
D) voltage gradients
Question
A junction box for an underwater application shall be comprised of ____, brass, suitable plastic, or other approved corrosion-resistant material.

A) stainless steel
B) aluminum
C) tin
D) copper
Question
Where a permanently installed pool is installed, no fewer than one 125-volt 15- or 20-ampere receptacle on a general-purpose branch circuit shall be located a minimum of ____ ft, but no more than 20 ft, from the pool's inside wall.

A) 5
B) 6
C) 8
D) 12
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/25
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 19: Specific Equipment
1
Article 647 covers the installation and wiring of sensitive electronic equipment that is connected to a separately derived system operating at ____ volts line-to-line and 60 volts to ground.

A) 100
B) 112
C) 120
D) 180
C
2
Each hoistway elevator pit shall have at least one ____-volt, single phase, 15- or 20-ampere duplex receptacle

A) 100
B) 120
C) 125
D) 140
C
3
An electric vehicle supply equipment's coupling means shall be stored or located at a height of not less than ____ in. above the floor level for indoor locations and 24 in. above the grade level for outdoor locations.

A) 12
B) 14
C) 18
D) 24
C
4
Individual office furnishings of the freestanding type, or groups of individual office furnishings that are electrically connected, are mechanically contiguous, and do not exceed 30 ft when assembled, shall be permitted to connect to the building's electrical system by means of a ____.

A) single flexible cord and plug
B) rigid raceway
C) surge protector and concealed wiring
D) dual flexible cable and panel board
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
5
Electric signs and outline lighting systems shall be marked with the manufacturer's name, trademark or other identification, ____, and current rating.

A) input voltage
B) output wattage
C) potential lumens
D) average load
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
6
Equipment used to combine and level-match a multiplicity of electronic signals, as from microphones, electronic instruments, and recorded audio is referred to as a(n) ____.

A) panel board
B) mixer
C) audio swapper
D) signal transformer
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
7
Conductors in pipe organs shall have ____ insulation.

A) standard polymer
B) thermoplastic or thermosetting
C) thermoelastic or thermo-molded
D) hybrid plastic/polymer
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
8
Circuit voltage of heating/air-conditioning equipment branch circuits located on the elevator car shall not exceed ____ volts.

A) 500
B) 600
C) 800
D) 1000
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
9
A separately derived ____ with 60 volts on each of two ungrounded conductors to a grounded neutral conductor can be used to reduce objectionable noise in sensitive electronic equipment locations.

A) 110-volt, single-phase, 3-wire system
B) 115-volt, single-phase, 3-wire system
C) 120-volt, single-phase, 3-wire system
D) 125-volt, single-phase, 3-wire system
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
10
Flexible metal conduit, ____ metal conduit, liquidtight flexible nonmetallic conduit, and flexible cords and cables are permitted wiring methods are permitted on the counterweight assembly and on the car assembly in elevators.

A) rigid sealed
B) flexible hybrid
C) liquidtight flexible
D) liquidtight rigid
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
11
Branch circuits and feeders in a separately derived 60-volts to ground system shall be provided with a means to ____.

A) prevent current surges
B) simultaneously disconnect all ungrounded conductors
C) protect from lightening discharges
D) permit service access
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
12
LFNC of ____ in. nominal trade size or larger, as defined in 356.2(2), can be installed in escalators or moving walkways in lengths greater than 6 ft.

A) 1/4
B) 3/8
C) 5/8
D) 3/4
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
13
Neon tubing's length and design shall not cause a continuous overcurrent beyond the capacity of the transformer or ____.

A) surge protection
B) disconnecting means
C) electronic power supply
D) branch circuit
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
14
Electric signs and outline lighting system equipment in wet locations, unless of the listed watertight type, shall be weatherproof and, if necessary, have ____ in accordance with 600.9(D)(1) through (3).

A) surge protection
B) lightening protection
C) a front-mounted disconnect
D) drain holes
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
15
The minimum conductor size for traveling cables that feed lighting circuits is ____ AWG copper.

A) 14
B) 16
C) 18
D) 20
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
16
Neon tubing secondary conductor(s) shall be supported within ____ in.of the electrode connection.

A) 4
B) 6
C) 12
D) 18
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
17
A luminaire intended for installation in a pool or fountain structure's forming shell, where completely surrounded by water is referred to as ____.

A) a wet niche luminaire
B) aquatic luminaire
C) forming shell
D) packaged source
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
18
A pipe organ should use a minimum of ____ AWG conductors for electronic signal circuits, and at least 26 AWG for electromagnetic valve supply.

A) 24
B) 26
C) 28
D) 30
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
19
All ____ receptacle outlets used in technical applications shall be GFCI protected.

A) 15- and 20-ampere
B) 15- and 25-ampere
C) 15- and 30-ampere
D) 20- and 30-ampere
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
20
The power source for a pipe organ shall be a transformer-type rectifier having a direct current (dc) potential of ____ volts or less.

A) 10
B) 20
C) 25
D) 30
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
21
Unit heaters shall not be mounted over the pool or`within the area extending ____ ft horizontally from the inside walls of a pool.

A) 5
B) 6
C) 8
D) 9
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
22
Unencapsulated structural reinforcing steel in pools shall be ____.

A) bonded together by steel tie wires or the equivalent
B) grounded via rigid wire cables to an earth ground
C) bonded using equipotential bonding
D) encased in corrosion-resistant materials
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
23
Equipotential bonding required by 680.26 shall be installed to reduce ____ in the pool area.

A) power surges
B) shorting
C) load
D) voltage gradients
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
24
A junction box for an underwater application shall be comprised of ____, brass, suitable plastic, or other approved corrosion-resistant material.

A) stainless steel
B) aluminum
C) tin
D) copper
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck
25
Where a permanently installed pool is installed, no fewer than one 125-volt 15- or 20-ampere receptacle on a general-purpose branch circuit shall be located a minimum of ____ ft, but no more than 20 ft, from the pool's inside wall.

A) 5
B) 6
C) 8
D) 12
Unlock Deck
Unlock for access to all 25 flashcards in this deck.
Unlock Deck
k this deck