Exercise 100
An industrial load requires 40 kW at 0.84 pf lagging. The load voltage is 220 0° V rms at 60 Hz. The transmission-line impedance is 0.1 + j 0.25 . Determine the real and reactive power losses in the line and the real and reactive power required at the input to the transmission line.
Explanation
Verified
like image
like image

Consider Figure 1.
blured image Consider the expres...