Exercise 35
A balanced three-phase source supplies power to three loads:
Load 1: 24 kW at 0.8 pf lagging
Load 2: 10 kVA at 0.7 pf leading
Load 3: unknown
If the line voltage at the load is 208 V rms, the magnitude of the total complex power is 41.93 kVA, and the combined power factor at the load is 0.86 lagging, find the unknown load.
Explanation
Verified
like image
like image

Consider the expression for
blured image .
blured image Subst...