Exam 7: Introduction to Residential Service Entrances

arrow
  • Select Tags
search iconSearch Question
flashcardsStudy Flashcards
  • Select Tags

The NEC requires a minimum clearance of __________ feet above residential property and driveways where the voltage to ground does not exceed 300 volts.

(Multiple Choice)
4.9/5
(33)

Explain why a seal is required anytime a raceway containing electrical conductors is installed from a cold area to a warm area.

(Essay)
4.9/5
(38)

A supplemental grounding electrode is a grounding electrode used to "back-up" a metal water pipe grounding electrode.

(True/False)
4.7/5
(35)

One set of service entrance conductors is permitted to supply __________ service disconnecting means instead of a single main disconnect.

(Multiple Choice)
4.8/5
(40)

Direct-buried conductors emerging from the ground must be protected to a point at least __________ feet above finished grade.

(Multiple Choice)
4.9/5
(36)

Overhead service conductors are permitted to be attached to trees for support.

(True/False)
4.8/5
(36)

A(n) __________ is the conductor connected to the neutral point of a system and is intended to carry current under normal conditions.

(Multiple Choice)
4.8/5
(30)

The enclosure housing a temporary service entrance disconnecting means must be dust-tight.

(True/False)
4.9/5
(44)

If a concrete-encased electrode is used, the end of the 4 AWG copper conductor or the end of the re-bar (whichever is used) can be extended from its location in the concrete to an accessible location above the concrete.

(True/False)
4.7/5
(31)

A coupling connecting two conduits together for a service mast can be located above the last point of securement to the house.

(True/False)
4.8/5
(37)

The overhead service conductors from the last pole to the point connecting them to the service entrance conductors at the building are called __________ conductors.

(Multiple Choice)
4.8/5
(31)

Copper-coated steel ground rods must be listed and be at least __________ in diameter.

(Multiple Choice)
4.9/5
(45)

According to NEC Table 250.66, the minimum size copper grounding electrode conductor for a service entrance installed with 4/0 copper conductors is__________.

(Multiple Choice)
4.9/5
(35)

When a warning ribbon is required to mark the location of buried underground service conductors, it must be placed at least __________ inches above the buried conductors.

(Multiple Choice)
4.8/5
(32)

_______________ is the term for being connected together to establish electrical continuity and conductivity.

(Essay)
4.7/5
(36)

A length of raceway that extends up a utility pole and encloses the service entrance conductors in an underground service is called a(n) _______________.

(Essay)
4.7/5
(42)

__________ is a general term used for material, fittings, devices, appliances, lighting fixtures, apparatus, machinery, and other parts used in connection with an electrical installation.

(Multiple Choice)
4.7/5
(34)

Explain why the NEC and local utility companies require the service entrance disconnecting means, if located inside a house, to be installed as close as possible to where the service conductors enter the house.

(Essay)
4.8/5
(42)

The NEC requires a clearance of at least __________ feet above final grade for service conductors where they are connected to the building, above sidewalks and other areas accessible to pedestrians.

(Multiple Choice)
4.8/5
(36)

If a single grounding electrode that is a rod, pipe, or plate does not have resistance to earth of 25 ohms or less, an additional electrode must be installed.

(True/False)
4.9/5
(34)
Showing 21 - 40 of 48
close modal

Filters

  • Essay(0)
  • Multiple Choice(0)
  • Short Answer(0)
  • True False(0)
  • Matching(0)