Exam 6: Determining Branch Circuit, Feeder Circuit, and Service Entrance Requirements
Exam 1: Residential Workplace Safety47 Questions
Exam 2: Hardware and Materials Used in Residential Wiring53 Questions
Exam 3: Tools Used in Residential Wiring46 Questions
Exam 4: Test and Measurement Instruments Used in Residential Wiring51 Questions
Exam 5: Understanding Residential Building Plans41 Questions
Exam 6: Determining Branch Circuit, Feeder Circuit, and Service Entrance Requirements49 Questions
Exam 7: Introduction to Residential Service Entrances48 Questions
Exam 8: Service Entrance Equipment and Installation42 Questions
Exam 9: General Nec Requirements for Rough-In Wiring49 Questions
Exam 10: Electrical Box Installation44 Questions
Exam 11: Cable Installation49 Questions
Exam 12: Raceway Installation47 Questions
Exam 13: Switching Circuit Installation44 Questions
Exam 14: Branch-Circuit Installation47 Questions
Exam 15: Special Residential Wiring Situations49 Questions
Exam 16: Video, Voice, and Data Wiring Installation52 Questions
Exam 17: Lighting Fixture Installation52 Questions
Exam 18: Device Installation46 Questions
Exam 19: Service Panel Trim-Out42 Questions
Exam 20: Checking Out and Troubleshooting Electrical Wiring Systems41 Questions
Exam 21: Green Wiring Practices32 Questions
Exam 22: Photovoltaic Pv System Installation44 Questions
Select questions type
According to Section 310.15(B)(7) in the NEC, the minimum conductor size for a 300-ampere residential service entrance is _________ Cu or _________ Al.
(Multiple Choice)
4.8/5
(32)
In residential wiring, which of the following house areas does not have its power supplied by a small appliance circuit?
(Multiple Choice)
4.9/5
(35)
Which of the following is not permitted to be connected to a small appliance branch circuit?
(Multiple Choice)
4.7/5
(47)
A circuit that consists of two or more ungrounded conductors that have a voltage between them, and a grounded conductor that has equal voltage between it and each ungrounded conductor of the circuit is called a multiwire circuit.
(True/False)
4.9/5
(34)
A house will have a counter-mounted cooking unit with a nameplate rating of 4 kW and a wall-mounted oven with a nameplate rating of 6 kW.A separate individual branch circuit will be run to the counter-mounted cooking unit and to the wall-mounted oven.What is the branch circuit load for each of the appliances in amperes?
(Essay)
4.7/5
(37)
When cables or conductors are physically tied, wrapped, or taped together, they are considered to be ______________.
(Multiple Choice)
4.9/5
(33)
According to Table 310.15(B)(16) in the NEC, the ampacity for a 3 AWG copper conductor using the 75 degree Celsius column is ____________.
(Multiple Choice)
4.8/5
(33)
Which of the following loads does not require a grounded circuit conductor?
(Multiple Choice)
4.8/5
(40)
A 1900 square foot residence has a general lighting load of ____________________ volt-amperes.
(Essay)
4.9/5
(40)
A house will have an electric range that has a nameplate rating of 14 kW.What is the load used to calculate the branch circuit rating?
(Essay)
4.8/5
(27)
When doing a standard service entrance calculation and applying the demand factor to the total load of the general lighting load, the small appliance circuits, and the laundry circuit, the first ___________ volt-amperes are computed at 100%.
(Multiple Choice)
4.9/5
(29)
According to the NEC, the unit load used to calculate the minimum number of general lighting branch circuits in a dwelling is __________ volt-amperes per square foot.
(Multiple Choice)
4.9/5
(42)
According to Section 310.15(B)(7)(1), for one-family dwelling service entrance ratings of 100 through 400 amperes the service conductors can have a rating of _____ percent of the service rating.
(Multiple Choice)
4.7/5
(43)
When doing a standard service entrance calculation, if a residence has four fixed appliances, a demand factor of __________% is applied to the total load of these appliances.
(Multiple Choice)
4.9/5
(42)
If cables are bundled together for more than 24 inches and the total number of current-carrying conductors exceeds __________, the ampacity of the conductors must be derated.
(Multiple Choice)
4.9/5
(36)
According to Section 310.15(B)(7) in the NEC, the minimum conductor size for a 200-ampere residential service entrance is _________ Cu or _________ Al.
(Multiple Choice)
4.9/5
(34)
Kitchen lighting outlets are permitted to be connected to any of the small-appliance branch circuits that provide power for the kitchen receptacles.
(True/False)
4.9/5
(26)
Dividing the total computed load in volt-amperes by the residential service voltage of ____________________ volts will give the minimum ampacity that the service conductors must be rated for.
(Essay)
4.7/5
(27)
All of the following types of branch circuits are found in residential wiring except:
(Multiple Choice)
4.9/5
(36)
An area including a basin with one or more of the following: a toilet, a urinal, a tub, a shower, a bidet, or similar plumbing fixtures is called a bathroom according to the NEC.
(True/False)
4.8/5
(30)
Showing 21 - 40 of 49
Filters
- Essay(0)
- Multiple Choice(0)
- Short Answer(0)
- True False(0)
- Matching(0)