Exam 12: Panelboard Selection and Installation

arrow
  • Select Tags
search iconSearch Question
  • Select Tags

For electrical equipment not considered large, at least ____  entrance(s)of sufficient area is required to provide access to and egress from the working space.

Free
(Multiple Choice)
4.7/5
(43)
Correct Answer:
Verified

A

What are the requirements for panelboard cabinet sizing?

Free
(Essay)
4.9/5
(26)
Correct Answer:
Verified

If there are special requirements for using the wiring gutters in a panelboard, the physical size of the cabinet is required to be sufficient to accommodate those requirements. Often a feeder serves two or more panelboards, in which case either a junction box or wireway is installed or the feeder connects to the first panelboard and then is extended to the others. In some cases, double lugs are installed for the phase conductors and neutral, if used. Other designs have feed-through lugs with the supply-side feeder conductors connected to the line terminals of the first panelboard and conductors of the same size connected from the load terminals of the first panelboard to the line terminals of the second panelboard. Both methods require the installation of additional feeder conductors. The cabinet must have sufficient gutter width for bending these conductors and for the required splices if splices are made.

All working spaces must allow for the opening of equipment doors and hinged panels to at least a ____ degree position.

Free
(Multiple Choice)
4.9/5
(32)
Correct Answer:
Verified

C

What are the requirements for preparing a circuit directory?

(Essay)
4.9/5
(29)

The circuit directory gives the ____ for each circuit in a wording that would be clear for "nonelectrical" people to decipher and identify the circuit number for luminaires, receptacles, appliances, or equipment.

(Multiple Choice)
4.8/5
(39)

Often a feeder serves two or more panelboards, in which case either a(n)____ or wireway is installed or the feeder connects to the first panelboard and then is extended to the others.

(Multiple Choice)
4.8/5
(43)

​If more than one system voltage is used for premises wiring, how should panelboards be marked?

(Essay)
4.9/5
(37)

What is the difference between past and current usages of the term panelboard?

(Essay)
4.8/5
(39)

The reasoning for identifying the system voltage(s)and phases is ____.

(Multiple Choice)
4.8/5
(30)

Unused openings in panelboards and switches should be ____.

(Multiple Choice)
4.9/5
(32)

Working space height is required to not be less than ____ ft.

(Multiple Choice)
4.8/5
(29)

What are the three conditions related to live parts and working space?

(Essay)
4.9/5
(41)

Panelboard ratings are determined by the ____ capacity of the internal main bus.

(Multiple Choice)
4.8/5
(31)

NEC 408.36(A)stipulates that if the panelboard contains snap switches with a rating of ____ amperes or less, the panelboard overcurrent protection is not permitted to exceed 200 amperes.

(Multiple Choice)
4.8/5
(42)

Conductors for 480Y/277-volt systems are generally brown, orange, ____ for the ungrounded conductors and gray for the grounded conductor..

(Multiple Choice)
4.9/5
(42)

The feeder overcurrent protection is sized for the ____ of the feeder conductor.

(Multiple Choice)
4.8/5
(31)

Separate feeders are to be run from the main service equipment to each of the areas of the commercial building. Each feeder will terminate in a ____, which generally will be installed in the area to be served.

(Multiple Choice)
4.8/5
(30)

For system voltages of 0 to 150 volts to ground, the minimum depth of working space is ____ ft under all three working space conditions.

(Multiple Choice)
4.7/5
(39)

Most large commercial buildings use two voltages: 480Y/277 volts and ____/120 volts.

(Multiple Choice)
4.9/5
(41)

In general, panelboards are constructed so the ____ run vertically for nearly the height of the panelboard.

(Multiple Choice)
4.9/5
(33)
close modal

Filters

  • Essay(0)
  • Multiple Choice(0)
  • Short Answer(0)
  • True False(0)
  • Matching(0)