Exam 4: Branch Circuits
Exam 1: Commercial Building Plans and Specifications20 Questions
Exam 2: Reading Electrical Working Drawings- Entry Level20 Questions
Exam 3: Calculating the Electrical Load20 Questions
Exam 4: Branch Circuits20 Questions
Exam 5: Switches and Receptacles20 Questions
Exam 6: Wiring Methods20 Questions
Exam 7: Motor and Appliance Circuits20 Questions
Exam 8: Feeders20 Questions
Exam 9: Special Systems20 Questions
Exam 10: Working Drawings- Upper Level20 Questions
Exam 11: Special Circuits Owners Circuits20 Questions
Exam 12: Panelboard Selection and Installation20 Questions
Exam 13: The Electric Service20 Questions
Exam 14: Lamps and Ballasts for Lighting20 Questions
Exam 15: Luminaires20 Questions
Exam 16: Emergency, Legally Required Sstandby, and Optional Standby Power Systems20 Questions
Exam 17: Overcurrent Protection: Fuses and Circuit Breakers20 Questions
Exam 18: Short-Circuit Calculations and Coordination of Overcurrent Protective Devices20 Questions
Exam 19: Equipment and Conductor Short-Circuit Protection20 Questions
Exam 20: Low-Voltage Remote-Control20 Questions
Exam 21: The Cooling System20 Questions
Exam 22: Commercial Utility Interactive Photovoltaic Systems20 Questions
Select questions type
Multioutlet branch-circuit ratings are limited to 15-, 20-, 30-, 40-, and 50-ampere except on premises, where they may have a higher rating.
Free
(Multiple Choice)
4.9/5
(41)
Correct Answer:
D
When all conductors of the same alternating-current circuit are in the same raceway, the magnetic flux around each conductor the magnetic flux of the other circuit conductors.
Free
(Multiple Choice)
4.8/5
(36)
Correct Answer:
B
Law proves that in a given circuit, the higher the impedance, the lower the current flow.
Free
(Multiple Choice)
4.8/5
(41)
Correct Answer:
A
During the process of laying out an electrical system, when are branch circuits assigned?
(Essay)
5.0/5
(28)
Although several different types of insulation are listed in the NEC, there are only three different temperature ratings: 60 degrees C, 75 degrees C, and degrees C.
(Multiple Choice)
4.9/5
(39)
Where would insulation with high-temperature rating be needed and why?
(Essay)
4.8/5
(28)
The allowable ampacity of a 4 AWG THHN conductor is 95 amperes.If we have four 4 AWG THHN conductors, what is the adjusted ampacity?
(Multiple Choice)
5.0/5
(39)
Whenever a grouping of more than current-carrying conductors exists, an adjustment factor from NEC Table 310.15(B)(3)(a) must be applied.
(Multiple Choice)
4.7/5
(37)
In general, the letter-type designation R formerly referred to a -based covering and now indicates thermoset insulation.
(Multiple Choice)
4.7/5
(42)
NEC Table 310.15(B)(16) places the wires available for building construction into two categories: and aluminum.
(Multiple Choice)
5.0/5
(41)
When sizing conductors and overcurrent protection, you must take 100 percent of the noncontinuous loads plus percent of the continuous loads.
(Multiple Choice)
4.8/5
(36)
Count the neutral conductor of a 4-wire, 3-phase, wye-connected circuit when the major portion of the load is electric discharge lighting (fluorescent, mercury vapor, high-pressure sodium, etc.), data processing, and other loads where the neutral conductor carries current.
(Multiple Choice)
4.8/5
(35)
Several factors or conditions can cause conductors to overheat, but often overlooked is the possibility of .
(Multiple Choice)
4.8/5
(39)
Metal raceways not properly grounded could become " " and present a shock hazard.
(Multiple Choice)
4.8/5
(40)
If the ambient temperature anywhere along the length of a raceway is less than 78 degrees F or higher than degrees F, the ampacity of the conductors in the raceway, or cable, must be modified by a correction factor.
(Multiple Choice)
4.7/5
(36)
How does oxidation affect aluminum conductors, and how can this be averted?
(Essay)
4.8/5
(30)
An exception to the rule where two different temperatures are encountered for the same conductors permits the application of the higher ampacity (lower temperature) if the length of the conductors that enter a higher temperature is not more than 10 ft (3.0 m) or not more than 10% of the total circuit length.
(Multiple Choice)
4.9/5
(38)
Filters
- Essay(0)
- Multiple Choice(0)
- Short Answer(0)
- True False(0)
- Matching(0)