Exam 17: Industrial Locations

arrow
  • Select Tags
search iconSearch Question
flashcardsStudy Flashcards
  • Select Tags

Means shall be provided to disconnect all conductors in a building (or other structure) from the ____.

Free
(Multiple Choice)
4.8/5
(31)
Correct Answer:
Verified

D

Overload is defined as operation of equipment in excess of normal, full-load rating, or of a conductor ____ that, when it persists for a sufficient length of time, would cause damage or dangerous overheating.

Free
(Multiple Choice)
4.8/5
(30)
Correct Answer:
Verified

B

The combined length of one primary plus one secondary conductor (excluding any portion of the primary conductor protected at its ampacity) shall not exceed ____.

Free
(Multiple Choice)
4.8/5
(35)
Correct Answer:
Verified

D

Wherever such an arrangement is practicable, transformer vaults shall be located so that ____.

(Multiple Choice)
4.8/5
(31)

If a crane, hoist, or monorail hoist operates above readily combustible material, specific requirements shall apply to ____.

(Multiple Choice)
4.8/5
(40)

A tap conductor is a ____ that exceeds the value permitted for similar conductors protected as otherwise described in 240.4.

(Multiple Choice)
4.8/5
(39)

____ branch circuits shall be protected at the motor nameplate current rating.

(Multiple Choice)
4.9/5
(37)

To calculate the ampacity of conductors supplying several motors (feeder conductors), multiply the largest motor full-load current (FLC) rating by ____% and add the FLC ratings of all other motors (or loads) in the group.

(Multiple Choice)
4.7/5
(43)

A ____ is the minimum size allowed if the overcurrent protection on the tap conductor's line side is 600 amperes.

(Multiple Choice)
4.7/5
(33)

Conductors used in the secondary circuit of electric welders shall have ____.

(Multiple Choice)
4.8/5
(27)

The capacitor circuit conductor's ampacity shall be at least ____% of the capacitor's rated current.

(Multiple Choice)
4.8/5
(33)

Barriers are required in all service-entrance motor-control centers to ____ and terminals from the remainder of the motor-control center.

(Multiple Choice)
4.7/5
(36)

Minimum ampacity of arc welder conductors supplying a group of welders shall be based on ____ as determined in 630.11(A)

(Multiple Choice)
4.9/5
(41)

Where multiple power supplies serve the same dc system, the dc side of each power supply shall have a ____.

(Multiple Choice)
4.8/5
(36)

Motor circuits rated 1000 volts, nominal, or less, shall have a disconnecting means with an ampere rating of at least ____% of the motor's full-load current rating.

(Multiple Choice)
4.7/5
(36)

A transformer vault door must be ____.

(Multiple Choice)
4.8/5
(33)

Cable tray systems should be ____.

(Multiple Choice)
4.8/5
(34)

Knife switches rated more than ____, and at over 1000 amperes at 251 to 1000 volts, shall be used only as isolating switches and shall not be opened under load.

(Multiple Choice)
4.9/5
(37)

Where an orderly shutdown is required to minimize the personnel/equipment hazard(s), a system of coordination based on the following two conditions is permitted: (1) coordinated short-circuit protection and (2) ____.

(Multiple Choice)
4.9/5
(29)

The tap conductor's ampacity shall not be less than the ____ on the circuits it supplies.

(Multiple Choice)
4.8/5
(31)
Showing 1 - 20 of 25
close modal

Filters

  • Essay(0)
  • Multiple Choice(0)
  • Short Answer(0)
  • True False(0)
  • Matching(0)