Exam 17: Industrial Locations
Exam 1: Introduction to the National Electrical Code13 Questions
Exam 2: Definitions25 Questions
Exam 3: Boxes and Enclosures25 Questions
Exam 4: Cables17 Questions
Exam 5: Raceways and Conductors26 Questions
Exam 6: General Provisions25 Questions
Exam 7: Specific Provisions25 Questions
Exam 8: Load Calculations25 Questions
Exam 9: Services and Electrical Equipment27 Questions
Exam 10: Comprehensive Provisions25 Questions
Exam 11: Load Calculations14 Questions
Exam 12: General Provisions25 Questions
Exam 13: Nondwelling Load Calculations17 Questions
Exam 14: Services, Feeders, and Equipment25 Questions
Exam 15: Hazardous Classified Locations25 Questions
Exam 16: Health Care25 Questions
Exam 17: Industrial Locations25 Questions
Exam 18: Special Occupancies25 Questions
Exam 19: Specific Equipment25 Questions
Select questions type
Means shall be provided to disconnect all conductors in a building (or other structure) from the ____.
Free
(Multiple Choice)
4.8/5
(31)
Correct Answer:
D
Overload is defined as operation of equipment in excess of normal, full-load rating, or of a conductor ____ that, when it persists for a sufficient length of time, would cause damage or dangerous overheating.
Free
(Multiple Choice)
4.8/5
(30)
Correct Answer:
B
The combined length of one primary plus one secondary conductor (excluding any portion of the primary conductor protected at its ampacity) shall not exceed ____.
Free
(Multiple Choice)
4.8/5
(35)
Correct Answer:
D
Wherever such an arrangement is practicable, transformer vaults shall be located so that ____.
(Multiple Choice)
4.8/5
(31)
If a crane, hoist, or monorail hoist operates above readily combustible material, specific requirements shall apply to ____.
(Multiple Choice)
4.8/5
(40)
A tap conductor is a ____ that exceeds the value permitted for similar conductors protected as otherwise described in 240.4.
(Multiple Choice)
4.8/5
(39)
____ branch circuits shall be protected at the motor nameplate current rating.
(Multiple Choice)
4.9/5
(37)
To calculate the ampacity of conductors supplying several motors (feeder conductors), multiply the largest motor full-load current (FLC) rating by ____% and add the FLC ratings of all other motors (or loads) in the group.
(Multiple Choice)
4.7/5
(43)
A ____ is the minimum size allowed if the overcurrent protection on the tap conductor's line side is 600 amperes.
(Multiple Choice)
4.7/5
(33)
Conductors used in the secondary circuit of electric welders shall have ____.
(Multiple Choice)
4.8/5
(27)
The capacitor circuit conductor's ampacity shall be at least ____% of the capacitor's rated current.
(Multiple Choice)
4.8/5
(33)
Barriers are required in all service-entrance motor-control centers to ____ and terminals from the remainder of the motor-control center.
(Multiple Choice)
4.7/5
(36)
Minimum ampacity of arc welder conductors supplying a group of welders shall be based on ____ as determined in 630.11(A)
(Multiple Choice)
4.9/5
(41)
Where multiple power supplies serve the same dc system, the dc side of each power supply shall have a ____.
(Multiple Choice)
4.8/5
(36)
Motor circuits rated 1000 volts, nominal, or less, shall have a disconnecting means with an ampere rating of at least ____% of the motor's full-load current rating.
(Multiple Choice)
4.7/5
(36)
Knife switches rated more than ____, and at over 1000 amperes at 251 to 1000 volts, shall be used only as isolating switches and shall not be opened under load.
(Multiple Choice)
4.9/5
(37)
Where an orderly shutdown is required to minimize the personnel/equipment hazard(s), a system of coordination based on the following two conditions is permitted: (1) coordinated short-circuit protection and (2) ____.
(Multiple Choice)
4.9/5
(29)
The tap conductor's ampacity shall not be less than the ____ on the circuits it supplies.
(Multiple Choice)
4.8/5
(31)
Showing 1 - 20 of 25
Filters
- Essay(0)
- Multiple Choice(0)
- Short Answer(0)
- True False(0)
- Matching(0)