Exam 9: Services and Electrical Equipment

arrow
  • Select Tags
search iconSearch Question
flashcardsStudy Flashcards
  • Select Tags

Panelboards shall be mounted in cabinets, cutout boxes, or identified enclosures and shall be ____.

Free
(Multiple Choice)
4.8/5
(27)
Correct Answer:
Verified

C

Entrance cables must be supported within ____ in. of every raceway or enclosure connection.

Free
(Multiple Choice)
4.9/5
(39)
Correct Answer:
Verified

B

Circuit breakers must have a voltage rating (clearly marked) ____ voltage.

Free
(Multiple Choice)
4.9/5
(36)
Correct Answer:
Verified

C

Type ____ cable can be formed in a gooseneck and taped with a self-sealing weather-resistant thermoplastic.

(Multiple Choice)
4.8/5
(36)

Cartridge fuses and fuseholders are classified according to ____.

(Multiple Choice)
4.9/5
(35)

Fuses must be plainly marked (by printing on or a label attached to the fuse barrel), showing the following: (1) ampere rating, (2) voltage rating, (3) ____, (4) "current-limiting" where applicable, and (5) the name or trademark of the manufacturer.

(Multiple Choice)
4.8/5
(39)

Splices in wire-type grounding electrode conductors are acceptable only if by means of irreversible compression-type connectors (listed as grounding and bonding equipment) or by the ____.

(Multiple Choice)
4.8/5
(39)

Panelboards include overcurrent devices as well as ____.

(Multiple Choice)
5.0/5
(32)

Although not stipulated in the NEC , some local jurisdictions have adopted ____ for service conductors.

(Multiple Choice)
5.0/5
(42)

Underground service conductors are defined as the underground conductors between the service point and the ____ to the service-entrance conductors in a terminal box.

(Multiple Choice)
4.8/5
(33)

Two to ____ circuit breakers or sets of fuses are acceptable as the overcurrent device to provide overload protection.

(Multiple Choice)
4.9/5
(28)

The radius of the curve of the inner edge of any bend in service-entrance cable must be at least ____ times the diameter of the cable.

(Multiple Choice)
4.8/5
(29)

Main bonding jumpers and system bonding jumpers must be made of ____ or other corrosion-resistant material.

(Multiple Choice)
4.9/5
(30)

Overhead service conductors, accessible only to pedestrian traffic, must have a minimum ____-ft vertical clearance above finished grade.

(Multiple Choice)
4.8/5
(41)

Working space illumination shall not be ____.

(Multiple Choice)
4.9/5
(38)

Wireways are ____ with hinged or removable covers used to house and protect electric wires and cables.

(Multiple Choice)
4.9/5
(39)

Circuit breakers and fuses can be connected in parallel provided they are ____.

(Multiple Choice)
4.8/5
(31)

Type USE cable used for service laterals can ___.

(Multiple Choice)
4.9/5
(34)

Voltage between overhead conductors does not exceed ____ volts.

(Multiple Choice)
4.9/5
(34)

Conductor sizes are expressed in American Wire Gage (AWG) or in ____.

(Multiple Choice)
4.9/5
(32)
Showing 1 - 20 of 27
close modal

Filters

  • Essay(0)
  • Multiple Choice(0)
  • Short Answer(0)
  • True False(0)
  • Matching(0)